ꁆ ꁇ
BESFULSolar water heating system (pressure type) type

D-315R Pressurized Solar Water Heating System Controller (RS485)

D315R is designed specifically for intelligent control of closed single-tank solar water-heating systems, with three functional modules: collector differential-temperature circulation, tank constant-temperature control, and return-pipe heat retention (or collector-pipe freeze protection).
Export SupportContact our Export Department for specifications, quotations, samples and shipping arrangements.

Product Details

D315R is designed specifically for intelligent control of closed single-tank solar water-heating systems, with three functional modules: collector differential-temperature circulation, tank constant-temperature control, and return-pipe heat retention (or collector-pipe freeze protection).

D315R features a MODBUS485 communication interface for communication with a host PLC, allowing all temperatures and setting parameters to be modified and read by the host.

Product

Product key features

  • Function 1: Differential-temperature heat-collection circulation between the solar collector and heat-collection tank, with protection functions: high-tank-temperature circulation stop, collector freeze-protection circulation, and protection against tube bursting caused by an excessive collector-tank temperature difference

  • Function 2: Thermostatic control of insulated water tank

  • Function 3: Independent temperature control for heat-tracing cables on collector or return-water pipes, providing freeze protection or return-water heat retention

  • Both heat-collection circulation and electric heating use high-current relay outputs. The heat-collection circulation output can directly drive a 500W pump, and the tank constant-temperature heating output can directly drive a 2000W electric heater.

  • The collector temperature probe uses an NTC230K thermistor with a high-temperature-resistant design, withstanding temperatures up to 250°C

  • The water tank temperature probe uses a waterproof sensor and can be immersed directly in water for measurement, with no waterproof thermowell required.

  • Collector temperature, water tank temperature, and other thermostat temperature measurements are all displayed to one decimal place

  • Three-way temperature measurement deviation correction

  • Intelligent power supply design automatically adapts to AC80V–240V for stable, durable, uninterrupted operation worldwide.

  • MODBUS-RS485 communication at 9600 baud. An external PLC host or our D-315R-PX7 seven-inch monitoring screen can read all measured temperatures and output states and set parameters.

Typical Product Applications

Product Technical Parameters

Operating power supply AC80~240V,AC/50HZ/60HZ
Power Consumption works 5 watts, standby < 2 watts
Storage Environment 40℃~70℃;5% to 95% non-condensing
Work environment 0℃~40℃;10% to 90% non-condensing
Display mode Digital Module
Buttons Silicone buttons
Temperature sensor High-temperature sensor T0: thermistor R(25℃)=230KΩ±1% B(100/200℃)=4537K±1%.
Standard temperature sensors T1, T2: thermistor R(25°C)=10KΩ±1%, B=3435
Temperature Measurement Range Collector temperature sensorT0: -10.0~250.0℃
Tank temperature sensorT1: -20.0~150.0℃
Temperature-control sensorT2: -20.0~150.0℃
Measurement accuracy ±1℃.
Show resolution ±0.1℃, temperature drift <0.3FS%
Output Collector circulation output: 30A, 250VAC (resistive load), relay ON/OFF, electrical life 100,000 cycles
Water tank constant-temperature output: 30A, 250VAC (resistive load), relay ON/OFF, electrical life 100,000 cycles
Temperature control output: 5A, 250VAC (resistive load), relay ON/OFF, electrical life 100,000 cycles
Other Flash memory technology retains parameter settings for extended periods after power loss

Product packaging, specifications and weight

Exterior dimensions 100mm (Length) x 100mm (Width) x 70mm (Height)
Net Weight 289.5g
Gross Weight 399 g
↑