BF-912A+ is a fully automatic controller for pumping, drainage, and water filling. It automatically controls water supply, provides low-water protection, and is suitable for a wide range of drainage and pumping applications.
Uses microcomputer IC control with staged water level control for upper and lower reservoirs (water towers) in high-rise buildings.Enables automatic refilling of a water tank (water tower) or automatic drainage, as well as joint control of upper and lower reservoirs;Effectively prevents pool overflow caused by excessive water levels and pump damage from dry running; suitable for industrial and household applications.
Ideal for unattended automatic pumping for water towers and wells serving cities, rural areas, schools, industrial and mining enterprises, and households. Also widely used in dyeing, chemical, food, beverage, brewing, sugar-making, and other industries.
★ Fully automatic water supply: stops when the tank is full and starts automatically when water is low.
★ Water-shortage protection prevents pump damage from dry running and heater damage caused by dry firing when the tank is empty.
★ Also convenient for drainage and pumping applications, such as municipal ditches and ponds.
★ Supports coordinated control of dual water tanks (sources), such as pumping from a small tank (source) to a large storage tank.
BF-912A+ offers two mounting methods, DIN-rail and screw-fixed, for easy maintenance.
Input for one AT35-3 or AT35-5 water level sensor set
All the way normally open and normally closed contact output
Upper/lower liquid level control water supply
Upper/lower level control pumping
Single level control water supply
Up/down dual water tank joint control
Anti-air pumping function
Water shortage and anti-dry burning function
Typical Product Applications
Product Technical Parameters
| Operating Power and Power Consumption |
AC220V ± 10%, 2 watts |
| Usage environment |
-10℃~50℃ |
| Input |
Five water level probe signal inputs: A, B, C, D, and E A is the upper limit input of the upper water tank B is the lower limit input of the upper water tank C is public pole D is the lower limit input of the drain tank E is the upper limit input of the drain tank |
| Output |
1. Relay normally open and normally closed contact output 2. The relay contact is rated at 6A for resistive loads and 1A for inductive loads.Can control a 1000W electric heater or a 200W motor or water pump, Larger loads require AC contactor expansion. |
| Other Parameters |
1. Set parameters Power off Long-term memory retention |
Product packaging, specifications and weight
| Product Packaging List |
1. Host 2.User Manual |
| Appearance dimension (mm) |
L 78 x W 41 x H 59 |
| Installation and dimensions (mm) |
The controller can be mounted on a standard DIN rail or fixed in place; the fixed-base mounting holes are spaced 72.6 mm apart |
| Weight |